Installing
4.3 Installing Power Modules
4.3.2

Dimensioned drawings, drilling dimensions for the PM240-2 Power Module, IP20

The following dimension drawings and drilling patterns are not to scale.
Frame sizes FSA ... FSC
Table 4-1
Frame
size
FSA
FSB
FSC
BOP-2, IOP-2 or blanking cover
1)
Power Module depth without Control Unit: 165 mm
2)
Table 4-2
Frame
size
FSA
FSB
FSC
The Power Module is designed for mounting without any lateral cooling air clearance. For tolerance
1)
reasons, we recommend a lateral clearance of approx. 1 mm.
62
Dimensions depend on the operator panel (OP) that is inserted
Width
Height [mm]
[mm]
without shield
plate
73
196
100
292
140
355
Drilling dimensions, cooling clearances and fixing
Drilling dimensions [mm]
h
b
c
186
62.3
6
281
80
6
343
120
6
Mounting depth in the cabinet with
with shield plate
276
370
432
Cooling air clearances [mm]
Top
Bottom
80
100
80
100
80
100
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Control Unit (CU) [mm]
without OP
with OP
227
238
227
238
227
238
Fixing/torque [Nm]
1)
Front
100
3 x M4 / 2.5
100
4 x M4 / 2.5
100
4 x M5 / 3.5
2)
1)