X500 And X501 Drive-Cliq Interface; X514 Power Supply For Digital Outputs And Sensors - Siemens SINAMICS S120 Combi Equipment Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Additional circuit examples are included in:
● SINAMICS S120 Safety Integrated Function Manual
● System Manual: The safety program for world industry,
9.1.3.3

X500 and X501 DRIVE-CLiQ interface

Table 9- 2
DRIVE-CLiQ interfaces X500 and X501
Pin
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interfaces included in the scope of delivery;
blanking plate (50 pieces) order number: 6SL3066-4CA00-0AA0
9.1.3.4

X514 power supply for digital outputs and sensors

Table 9- 3
Terminals for the power supply X514
Terminal
+
+
M1
M1
Max. connectable cross-section: 2.5 mm²
Type: Screw terminal 3 (see Chapter "Control cabinet installation and EMC / connection system")
1) including the current consumption for the digital outputs and to supply the sensor
Note
The two "+" and "M1" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
SINAMICS S120 Combi
Manual, Edition 05.2010, 6SL3097-4AV00-0BP0
order number: 6ZB5000-0AA01-0BA1, 5 Edition,
Supplement: 6ZB5000-0AB01-0BA0
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Designation
Power supply
Power supply
Electronics ground
Electronics ground
Additional system components
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
Technical specifications
Voltage: 24 V DC (20.4 V – 28.8 V)
Current consumption: max. 4 A
Max. current via jumper in connector: 20 A
9.1 Terminal Module TM54F
1)