Number
Cause
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life expired ● Check the PROFINET connection.
F08510
Send configuration data not valid
A08511
Receive configuration data not valid
A08526
No cyclic connection
A08565
Consistency error affecting adjusta‐
ble parameters
A08800
PROFIenergy energy-saving mode
active
A13000
Licensing is not sufficient
F13010
Licensing is not sufficient
F13010
Licensing, function module not li‐
censed.
F13101
Know-how protection: Copy protec‐
tion cannot be activated
F30001
Overcurrent
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Remedy
● Check the PROFINET connection.
● Set the controller to RUN mode.
● If the fault occurs repeatedly, check the monitoring time set p2044.
● Check the PROFINET configuration
● Activate the control with cyclic operation.
● Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
● IP address, subnet mask or default gateway is not correct.
● IP address or station name used twice in the network.
● Station name contains invalid characters.
The PROFIenergy energy-saving mode is active.
The alarm automatically disappears when the energy-saving mode is exi‐
ted.
You are using functions that require a license, but you don't have the ap‐
propriate licenses.
Activating licensed functions (Page 492)
Options requiring a license are used in the inverter, and the licensing is not
sufficient.
At least one function module requiring a license is not licensed.
Deactivate the function module that is not licensed.
Insert a valid memory card.
Check the following:
● Motor data, if required, carry out commissioning
● Motor connection method (Υ / Δ)
● V/f operation: Assignment of rated currents of motor and Power Module
● Line quality
● Make sure that the line commutating reactor is connected properly
● Power cable connections
● Power cables for short-circuit or ground fault
● Power cable length
● Line phases
● Short-circuit at the Control Unit output terminals
If this doesn't help:
● V/f operation: Increase the acceleration ramp
● Reduce the load
● Replace the power unit
Alarms, faults and system messages
8.6 List of alarms and faults