Advanced commissioning
6.20 PID technology controller
Parameter
Table 6-51
Basic settings
Parameter
Description
p2200
BI: Technology controller en‐
able
r2294
CO: Technology controller
output signal
p2253
CI: Technology controller set‐
point 1
p2264
CI: Technology controller ac‐
tual value
p2257, p2258
Technology controller ramp-
up time and ramp-down time
[s]
p2274
Technology controller differ‐
entiation time constant T
p2280
Technology controller propor‐
tional gain K
p2285
Technology controller inte‐
gration time (integral time) T
Table 6-52
Limiting the output of the technology controller
Parameter
Description
p2297
CI: Technology controller
maximum limiting signal
source
p2298
CI: Technology controller
minimum limiting signal
source
p2291
CO: Technology controller
maximum limiting [%]
p2292
CO: Technology controller
minimum limiting [%]
286
Setting
1 signal: Technology controller is enabled.
Factory setting: 0
To interconnect the main speed setpoint with the technology controller
output, set p1070 = 2294.
Setpoint for the technology controller.
Example:
p2253 = 2224: Fixed setpoint p2201 is interconnected with the setpoint of
the technology controller.
p2220 = 1: The fixed setpoint p2201 is selected.
Factory setting: 0
Technology controller actual value.
Factory setting: 0
Factory setting: 0.0 s
The differentiation improves the rise time for very slow controlled varia‐
[s]
bles, e.g. a temperature control.
d
Factory setting: 0.0 s
Factory setting: 1.0
P
Factory setting: 30 s
d
Setting
Factory setting: 1084
Factory setting: 2292
Factory setting: 100 %
Factory setting: 0 %
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG