Activating Free Function Block; Further Information - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.14.5

Activating free function block

The free function blocks are not active in the factory setting.
Activating and interconnecting free function blocks
Precondition
You have configured the inverter with the "Free function blocks" function module.
Procedure
1. Activate the function block: Assign the function block to a runtime group of your choice.
Example: Assign ADD 0 to runtime group 1: p20096 = 1.
2. If you have assigned several function blocks to the same runtime group, define a sensible
run sequence within the runtime group.
Example: Calculate ADD 0 before ADD 1: p20097 < p20101.
3. Interconnect the inputs and outputs of the function block with the required signals in the
inverter.
You have activated a free function block and interconnected its inputs and outputs.
6.14.6

Further information

Application description for the free function blocks
Further information is provided on the Internet:
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Quick commissioning with a PC (Page 134)
FAQ (http://support.automation.siemens.com/WW/view/en/85168215)
Advanced commissioning
6.14 Free function blocks