You will find more information in the List Manual.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Explanation
Output load detection current limit (Factory setting: 0 A)
Output load detection delay time (Factory setting: 2000 ms)
Load monitoring response (Factory setting: 0)
0: Load monitoring deactivated
1: A07920 for torque/speed too low
2: A07921 for torque/speed too high
3: A07922 for torque/speed out of tolerance
4: F07923 for torque/speed too low
5: F07924 for torque/speed too high
6: F07925 for torque/speed outside the tolerance
Load monitoring speed threshold 1 (Factory setting: 150 rpm)
Load monitoring speed threshold 2 (Factory setting: 900 rpm)
Load monitoring speed threshold 3 (Factory setting: 1500 rpm)
Load monitoring torque threshold 1 upper (Factory setting:
1000000 Nm)
Load monitoring torque threshold 1 lower (Factory setting: 0 Nm)
Load monitoring torque threshold 2 upper (Factory setting:
1000000 Nm)
Load monitoring torque threshold 2 lower (Factory setting: 0 Nm)
Load monitoring torque threshold 3 upper (Factory setting:
1000000 Nm)
Load monitoring torque threshold 3 lower (Factory setting: 0 Nm)
Load monitoring delay time (Factory setting: 10 s)
Load monitoring configuration (factory setting: 1)
0: Monitoring deactivated
1: Torque and load failure monitoring
2: Speed and load failure monitoring
3: Load failure monitoring
Load monitoring speed deviation (Factory setting: 150 rpm)
Torque actual value filter time constant (Factory setting: 100 ms)