10.3
Technical data, PM240-2 Power Modules
Protective devices for the Power Module
The fuses listed in the following tables are examples of suitable fuses.
Additional components for branch protection are available in the Internet:
support.industry.siemens.com/cs/ww/en/view/109479152)
10.3.1
High overload - low overload PM240-2
Typical inverter load cycles
Figure 10-2
10.3.2
Ambient conditions
Property
Ambient conditions for transport in the transport packaging
Climatic ambient conditions
Mechanical ambient condi‐
tions
Protection against chemical
substances
Biological ambient condi‐
tions
Ambient conditions for long-term storage in the product packaging
Climatic ambient conditions
Protection against chemical
substances
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Branch protection and short-circuit strength according to UL and IEC
"Low Overload" and "High Overload" load cycles
Version
‑ 40 °C ... + 70 °C, according to Class 2K4 to EN 60721‑3‑2
maximum humidity 95% at 40 °C
Shock and vibration permissible according to 1M2 to EN 60721‑3‑2
Protected according to Class 2C2 to EN 60721‑3‑2
Suitable according to Class 2B1 to EN 60721‑3‑2
‑ 25 °C ... + 55 °C, according to Class 1K3 to EN 60721‑3‑1
Protected according to Class 1C2 to EN 60721‑3‑1
10.3 Technical data, PM240-2 Power Modules
Technical data
(https://
445