Status word 1 (ZSW1)
Bit Significance
0
1
2
3
4
5
6
7
8
9
10 1 = Comparison speed
11 1 = Torque limit not reached
12 Reserved
13 0 = Alarm, motor overtempera‐
14 1 = Motor rotates clockwise
15 0 = Alarm, inverter thermal
If you change over from another telegram to telegram 20, then the assignment of the previous
1)
telegram is kept.
Further information
Further information about USS is provided in the "Fieldbus" function manual.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
1 = Ready for switching on
1 = Ready
1 = Operation enabled
1 = Fault active
1 = OFF2 inactive
1 = OFF3 inactive
1 = Switching on inhibited ac‐
tive
1 = Alarm active
1 = Speed deviation within the
tolerance range
1 = Master control requested
reached or exceeded
ture
0 = Motor rotates counter-
clockwise
overload
Overview of the manuals (Page 519)
Remarks
Power supply switched on; electronics initialized;
pulses locked.
Motor is switched on (ON/OFF1 = 1), no fault is
active. With the command "Enable operation"
(STW1.3), the inverter switches on the motor.
Motor follows setpoint. See control word 1, bit 3. p2080[2] =
The inverter has a fault. Acknowledge fault using
STW1.7.
Coast down to standstill is not active.
Quick stop is not active.
It is only possible to switch on the motor after an
OFF1 followed by ON.
Motor remains switched on; no acknowledge‐
ment is necessary.
Setpoint / actual value deviation within the toler‐
ance range.
The automation system is requested to accept
the inverter control.
Speed is greater than or equal to the correspond‐
ing maximum speed.
Comparison value for current or torque has been
fallen below.
--
Internal inverter actual value > 0
Internal inverter actual value < 0
Advanced commissioning
6.7 Drive control via USS
Signal inter‐
connection in
the inverter
p2080[0] =
r0899.0
p2080[1] =
r0899.1
r0899.2
p2080[3] =
r2139.3
p2080[4] =
r0899.4
p2080[5] =
r0899.5
p2080[6] =
r0899.6
p2080[7] =
r2139.7
p2080[8] =
r2197.7
p2080[9] =
r0899.9
p2080[10] =
r2199.1
p2080[11] =
r0056.13 /
r1407.7
p2080[12] =
r0899.12
p2080[13] =
r2135.14
p2080[14] =
r2197.3
p2080[15] =