Alarms, faults and system messages
8.1 Operating states indicated on LEDs
Table 8-6
BF
Communication via Modbus or USS:
If the fieldbus monitoring is deactivated with p2040 = 0, the BF-LED remains dark, independent
of the communication state.
Description of the LED symbols for CANopen
390
Fieldbuses via RS 485 interface
Explanation
Data exchange between the inverter and control system is active
The fieldbus is active, however, the inverter is not receiving any process data
RDY
When LED RDY flashes simultaneously:
Inverter waits until the power supply is switched off and switched on again after a
firmware update
No fieldbus connection is available
RDY
When LED RDY flashes simultaneously:
Incorrect memory card
Firmware update failed
Firmware update is active
LED is bright
LED flashes slowly
LED flashes quickly
LED flashes in the "single flash" mode
LED flashes in the "double flash" mode
LED flashes with variable frequency
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG