Siemens SINAMICS G120 Operating Instructions Manual page 82

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.4 Connecting the line supply and motor
Figure 4-11
Table 4-15
Connection, cross-section and tightening torque for PM240-2 Power Modules
Inverter
FSA
Line system, motor
and braking resistor
FSB
FSC
FSD
Line and motor
Braking resistor
FSE
Line and motor
Braking resistor
FSF
Line and motor
Braking resistor
FSG
Line and motor
Braking resistor
80
Connection of the PM240-2 Power Module, 1 AC 200 V, FSD ... FSF
Connection
Plug connector
with screw termi‐
nals
Screw-type termi‐
nal
Screw-type termi‐
nal
Cable lug accord‐
ing to SN71322 for
M10 bolts
Screw-type termi‐
nal
Cable lug accord‐
ing to SN71322 for
M10 bolts
Screw-type termi‐
nal
Cross-section, tightening torque
Metric
1.5 ... 2.5 mm
, 0.5 Nm
2
1.5 ... 6 mm
, 0.6 Nm
2
6 ...16 mm², 1.3 Nm
10 ... 35 mm
,
2
2.5 ... 4.5 Nm
2.5 ... 16 mm
,
2
1.2 ... 1.5 Nm
25 ... 70 mm
,
2
8 ... 10 Nm
10 ... 35 mm
,
2
2.5 ... 4.5 Nm
35 ... 2 × 120 mm
,
2
22 ... 25 Nm
25 ... 70 mm
,
2
8 ... 10 Nm
35 ... 2 × 185 mm
,
2
22 ... 25 Nm
25 ... 70 mm
,
2
... 10 Nm
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Imperial
16 ... 14 AWG, 4.5 lbf in 8 mm
16 ... 10 AWG, 5.5 lbf in 8 mm
10 ... 6 AWG, 12 lbf in
8 ... 2 AWG,
22 ... 40 lbf in
20 ... 6 AWG,
10.5 ... 13 lbf in
6 ... 3/0 AWG,
71 ... 88.5 lbf in
8 ... 2 AWG,
22 ... 40 lbf in
1 AWG ... 2 × 4/0 AWG,
195 ... 221 lbf.in
6 ... 3/0 AWG,
71 ... 88.5 lbf in
1 AWG ... 2 × 350 MCM,
195 ... 221 lbf.in
6 ... 3/0 AWG,
71 ... 88.5 lbf in
Converter with the CU250S-2 Control Units
Stripped
insulation
length
10 mm
18 mm
10 mm
25 mm
18 mm
--
25 mm
--
25 mm

Advertisement

Table of Contents
loading

Table of Contents