Technical data
10.3 Technical data, PM240-2 Power Modules
Table 10-10 PM240-2, IP20, frame size D, 200 V ... 240 V 3 AC
Article No. without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight
Table 10-11 PM240-2, PT, frame size D, 200 V ... 240 V 3 AC
Article No. without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight
approx. 0.72 kW through the heatsink
1)
452
6SL3210-1PC24-2UL0
11 kW
40 A
42 A
7.5 kW
36 A
35 A
3NA3822 (63 A)
60 A
0.45 kW
55 l/s
17 kg
6SL3211-1PC26-8UL0
18.5 kW
64 A
68 A
15 kW
56 A
54 A
3NA3830 (100 A)
90 A
0.82 kW
1)
55 l/s
19.5 kg
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
6SL3210-1PC25-4UL0
15 kW
51 A
54 A
11 kW
43 A
42 A
3NA3824 (80 A)
70 A
0.61 kW
55 l/s
17 kg
Converter with the CU250S-2 Control Units
6SL3210-1PC26-8UL0
18.5 kW
64 A
68 A
15 kW
56 A
54 A
3NA3830 (100 A)
90 A
0.82 kW
55 l/s
17 kg