Table 10-12 PM240-2, IP20, frame size E, 200 V ... 240 V 3 AC
Article No. without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight
Table 10-13 PM240-2, PT, frame size E, 200 V to 240 V 3 AC
Article No. without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight
approx. 1.1 kW through the heatsink
1)
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
6SL3210-1PC28-0UL0
22 kW
76 A
80 A
18.5 kW
71 A
68 A
3NA3830 (100 A)
100 A
0.92 kW
83 l/s
26 kg
6SL3211-1PC31-1UL0
30 kW
98 A
104 A
22 kW
83 A
80 A
3NA3836 (160 A)
150 A
1.28 kW
1)
83 l/s
29 kg
10.3 Technical data, PM240-2 Power Modules
6SL3210-1PC31-1UL0
30 kW
98 A
104 A
22 kW
83 A
80 A
3NA3836 (160 A)
150 A
1.28 kW
83 l/s
26 kg
Technical data