Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Defining the function of an analog output
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the particular analog output via its index,
e.g. parameter p0771[0] is assigned to analog output 0.
Table 6-7
CO
r0021
r0024
r0025
A complete list of the connector outputs is provided in the List Manual.
Additional information is provided in the parameter list and in function diagram 2261 of the List
Manual.
Application example: Defining the function of an analog output
Advanced settings
You can manipulate the signal that you output via an analog output, as follows:
● Absolute-value generation of the signal (p0775)
● Signal inversion (p0782)
Additional information is provided in the parameter list of the List Manual.
176
Connector outputs (CO) of the inverter (selection)
Significance
Actual speed smoothed
Output frequency, smoothed
Output voltage smoothed
Overview of the manuals (Page 519)
CO
Significance
r0026
DC link voltage smoothed
r0027
Absolute actual current smoothed
To output the inverter output current via analog output 0, you
must interconnect AO 0 with the signal for the output current.
Set p0771 = 27.
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG