Siemens SINAMICS G120 Operating Instructions Manual page 73

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 4-14
Frame size
FSD without filter
FSD with filter
FSE without filter
FSE with filter
FSF without filter
FSF with filter
You can mount the Power Modules without any lateral cooling air clearance. For tolerance reasons,
1)
we recommend a lateral clearance of approx. 1 mm.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Drilling dimensions, cooling clearances and fixing
Drilling dimensions [mm] Cooling air clearances [mm]
b
h
235
325
235
419
235
405
235
541
300
598
300
898
4.3 Installing Power Modules
c
Top
Bottom
11
300
300
11
300
300
11
300
300
11
300
300
11
350
350
11
350
350
Installing
Fixing/torque
1)
[Nm]
Front
65
4 x M6 / 6
65
4 x M6 / 6
65
4 x M6 / 6
65
4 x M6 / 6
65
4 x M8 / 13
65
4 x M8 / 13
71