Advanced commissioning
6.5 Drive control via PROFIBUS or PROFINET
Parameter
p2079
r2050[0...11]
p2051[0...16] PROFIdrive PZD send word
204
Description
PROFIdrive PZD telegram selection extended
The following values apply if you have still not enabled the "Basic positioner" function
in the inverter:
1:
Standard telegram 1, PZD-2/2
2:
Standard telegram 2, PZD-4/4
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
999:
Free telegram configuration
The following values apply if you have enabled the "Basic positioner" function in the
inverter:
7:
Standard telegram 7, PZD-2/2
9:
Standard telegram 9, PZD-10/5
110:
SIEMENS telegram 110, PZD-12/7
111:
SIEMENS telegram 111, PZD-12/12
999:
Free telegram configuration
PROFIdrive PZD receive word
Received PZD (setpoints) in the word format
Sent PZD (actual values) in the word format
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG