Advanced commissioning
6.25 Motor protection with temperature sensor
Parameter
p0605
p0610
p0640
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.
332
Description
Mot_temp_mod 1/2 / sensor threshold and temperature value (factory setting: 145° C)
For monitoring the motor temperature using KTY84/Pt1000.
Motor overtemperature response (factory setting: 12)
Determines the inverter behavior when the motor temperature reaches the alarm
threshold p0604.
0:
Alarm (A07910), no fault
1:
Alarm A07910 and fault F07011
The inverter reduces the current limit.
2,
Alarm A07910 and fault F07011
12:
The inverter does not reduce the current limit.
Current limit [A]
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG