Installing
4.3 Installing Power Modules
Frame
size
FSF
FSG
The Power Module is designed for mounting without any lateral cooling air clearance. For tolerance
1)
reasons, we recommend a lateral clearance of approx. 1 mm.
The top and bottom cooling air clearances refer to the Power Module without shield plate
2)
64
Drilling dimensions [mm]
h
b
c
680
270
13
970.5
265
15
Cooling air clearances [mm]
Top
Bottom
2)
2)
300
350
300
350
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Fixing/torque [Nm]
1)
Front
100
4 x M8 / 25
100