Connecting The Inverter With The Pm250 Power Module - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.4 Connecting the line supply and motor
4.4.4

Connecting the inverter with the PM250 Power Module

Figure 4-13
Connecting the PM250 Power Module
Table 4-16
Connection, cross-section and tightening torque for PM250 Power Modules
Inverter
Line supply and motor connection
FSC
FSD
FSE
FSF
Connections for frame size FSC
84
Screw-type terminal
Cable lug
Cross-section and tightening torque
Metric
4 ...10 mm
, 2.3 Nm
12 ... 8 AWG, 20 lbf in
2
10 ... 35 mm
, 6 Nm
7 ... 2 AWG, 53 lbf in
2
25 ... 50 mm
, 6 Nm
3 ... 1 AWG, 53 lbf in
2
35 ... 120 mm
, 13 Nm 2 ... 4/0 AWG, 115 lbf in --
2
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Stripped
insulation
Imperial
length
10 mm
--
--

Advertisement