Advanced commissioning
6.26 Motor protection by calculating the temperature
Parameter Description
p0344
p0604
p0605
p0612
p0627
p0625
r0632
p0640
Further information is provided in the function charts 8016 and 8017 of the List Manual.
Thermal motor model 1 for synchronous motors
Further information about thermal motor model 1 for synchronous motors is provided in the
function charts 8016 and 8017 of the List Manual.
334
Motor weight (for thermal motor type) (factory setting: 0.0 kg)
Mot_temp_mod 2/KTY alarm threshold (factory setting: 130.0°
C)
Motor temperature > p0604 ⇒ fault F07011.
Mot_temp_mod 1/2 threshold (factory setting: 145.0° C)
Motor temperature > p0605 ⇒ alarm A07012.
Mot_temp_mod activation
.01
1 signal: Activate motor temperature model 2 for induc‐
tion motors
.09
1 signal: Activate motor temperature model 2 expansions
The inverter sets bit 09 = 1 after commissioning. If you
load the parameter settings for firmware version ≤ V4.6
into the inverter, bit 09 = 0 remains.
Motor overtemperature, stator winding (factory setting: 80 K)
Motor ambient temperature during commissioning (factory setting: 20° C)
Specification of the motor ambient temperature in °C at the instant of the motor data iden‐
tification.
Mot_temp_mod stator winding temperature [°C]
Current limit [A]
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
After selecting an induc‐
tion motor (p0300) or a
listed induction motor
(p0301) during the com‐
missioning, the inverter
sets the parameters to
values appropriate for
the motor.
The parameters are
write-protected for listed
motors (p0301 ≥ 0).