Siemens SINAMICS G120 Operating Instructions Manual page 376

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Saving the settings and series commissioning
7.2 Saving settings on a PC
Procedure with Startdrive when the safety functions are enabled
1. Save the project.
2. Select "Load to device".
3. Connect Startdrive online with the drive.
4. Press the "Start safety commissioning" button.
5. Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6. Press the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the inverter power supply.
10.Wait until all LEDs on the inverter go dark (no voltage condition).
11.Switch on the inverter power supply again.
You have transferred the settings from the PG to the inverter with Startdrive and have activated
the safety functions.
374
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG

Advertisement

Table of Contents
loading

Table of Contents