Advanced commissioning
6.18 Setpoints
Parameter
p0582
p0583
p0585
r0586
272
Description
Probe
Pulses per revolution (factory setting 1)
1)
Number of pulses per revolution.
Probe
Maximum measurement time (factory setting 10 s)
1)
Maximum measurement time for the probe. If there is no new pulse before the maxi‐
mum measuring time elapses, the inverter sets the actual speed value in r0586 to zero.
The time is restarted with the next pulse.
Probe
Gear ratio (factory setting 1)
1)
The inverter multiplies the measured speed by the gear ratio before displaying it in
r0586.
Probe
Actual speed value
1)
Result of the speed calculation.
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Converter with the CU250S-2 Control Units