Procedure with Startdrive
1. Go online.
2. Select "Online & diagnostics".
3. Select "Backing up/reset".
4. Select the settings as shown in the diagram.
5. Start data transfer
6. Wait until Startdrive has signaled that the data transfer has been completed.
7. Go offline.
8. Switch off the inverter power supply.
9. Wait until all LEDs on the inverter are dark.
10.Switch on the inverter power supply again.
Your settings become effective after switching on.
You have transferred your settings from a memory card to the inverter.
Procedure with the BOP-2
1. Remove any USB cable that is inserted in the inverter.
6. Switch off the inverter power supply.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
2. In the "OPTIONS" menu, select "FROM CRD".
3. Set the number of your data backup. You can back up 99 different settings
on the memory card.
4. Start data transfer with OK.
5. Wait until the inverter has transferred the settings from the memory card.
Saving the settings and series commissioning
7.1 Saving settings on a memory card