You can find more information in the parameter list and in function diagram 2251 of the List
Manual.
Dead band
With the control enabled, electromagnetic interference on the signal cable can cause the motor
to slowly rotate in one direction in spite of a speed setpoint = 0.
p0764[0]
p0764[1]
Using an analog input as digital input
An analog input can also be used as digital input.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Overview of the manuals (Page 519)
Analog inputs dead zone, AI 0 (factory setting: 0)
Analog inputs dead zone, AI 1 (factory setting: 0)
Digital inputs (Page 165)
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
The dead band acts on the zero crossover of
the analog input characteristic. Internally, the
inverter sets its speed setpoint = 0, even if
the signal at the analog input terminals is
slightly positive or negative. This prevents
the inverter from rotating the motor at a
speed setpoint = 0.