Communication with the controller even when the supply voltage on the Power Module is
switched off
You must supply the Control Unit with 24 V DC at terminals 31 and 32 if you wish to maintain
communication with the control system when the line voltage is switched off.
In the case of brief interruptions of the 24 V power supply, the inverter may signal a fault without
communications with the control system being interrupted.
4.5.12.3

Installing the GSD

Procedure
1. Save the GSD on your PC via one of the following methods.
– With Internet access:
– Without Internet access:
2. Unzip the GSD file on your computer.
3. Import the GSD in the engineering system of the controller.
You have now installed the GSD file in the engineering system of the controller.
4.5.12.4

Setting the address

Valid address area: 1 ... 125
You have the following options for setting the address:
● Using the address switch on the Control Unit:
Figure 4-21
The address switch has priority over the other settings.
● Using Startdrive or an operator panel via parameter p0918 (default setting: p0918 = 126)
It is only possible to change p0918 if an invalid address is set in the address switch.
If you are working with Startdrive, back up the settings so they are not lost if the power fails.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
Insert a memory card into the inverter.
Set p0804 to 12.
The inverter writes the GSD as zipped file (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
Address switch with example for bus address 10
4.5 Connecting the interfaces for the inverter control
Installing
119