Starting up fieldbus communication for ACS880
and ACS580 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by selecting the correct slot number in parameter
50.01 FBA A enable.
The selection must correspond to the slot where the adapter
module is installed. For example, if the adapter module is
installed in slot 1, you must select slot 1.
3. With parameter 50.02 FBA A comm loss func, select how the
drive reacts to a fieldbus communication break.
Note that this function monitors both communication between
the fieldbus master and the adapter module and
communication between the adapter module and the drive.
4. With parameter 50.03 FBA A comm loss t out, define the time
between communication break detection and the selected
action.
5. Select application-specific values for parameters 50.04 and
50.05. The allowed values are listed in the table below.
6. Set the FECA-01 configuration parameters in drive parameter
group 51. At the minimum, set the value of parameter
51.02 Profile according to the application.
7. Save the valid parameter values to permanent memory with
parameter 96.07 Parameter save manually.
8. Set the relevant drive control parameters to control the drive
according to the application. If the CiA 402 profile is used, set
and check all parameters as instructed in the table below.
9. Validate the settings made in parameter groups 51 with
parameter 51.27 FBA A par refresh.
Start-up 51