Table 25: Low voltage dual phase PDU for Oracle Flash Storage Systems
Low Voltage
kVA size
Marketing part number
Phase
Voltage input
Number of input cords and plug type
Number of data center receptacles and
type
Maximum input current for each cord
Outlet receptacles (number/type)
Outlet groups for each PDU
PDU power cord length
Table 26: Low voltage three-phase PDU for Oracle Flash Storage Systems
Low Voltage
kVA size
Marketing part number
Phase
Oracle FS System Hardware Specifications
2Ph (2W + ground)
10 kVA
7104982
1 Phase
No grounded neutral conductors are
provided in the two input cords.
2x [2Ph (2W+ground)], 208Vac, 50/60 Hz,
maximum. 24A per phase
Can be connected to input sources in the
range of 200V – 240V AC (nominal)
2x NEMA L6-30P
2x NEMA L6-30R
24A
42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
6
2 meters (6.6 feet)
PDU power cords are 4 m (13 ft) long, but
only 2 m (6.6 ft) are usable outside of the
cabinet.
3Ph (3W + ground)
15 kVA
7104979
3
No grounded neutral conductors are
provided in the input cords.