Table 10: Low Voltage Dual Phase Pdu For Oracle Flash Storage Systems - Oracle FS1-2 Installation Manual

Flash storage system
Hide thumbs Also See for FS1-2:
Table of Contents

Advertisement

distribution to the components. The PDUs must provide sufficient current to
meet the sum of the requirements for the Oracle FS System components.
Oracle PDUs might be purchased for use with non-Oracle racks. The Oracle FS
System component power cords have been designed to work with vertical style
Oracle or third party PDUs. Non-Oracle PDUs must be compatible with Oracle
component power cord lengths and plug types. Non-Oracle PDUs must be
mounted in a manner such that the power cords provided by Oracle might be
used and the PDUs do not obstruct the ability to replace field replaceable units
(FRUs) and customer serviceable units (CRUs).
While planning rack-space, ensure that adequate space is also allocated for the
PDUs, if using non-Oracle PDUs.
The following tables provide information on the various PDUs for the Oracle FS
Systems, with the assumption that there are two PDUs in each rack.
Note: The term "Ph" stands for "phase" in the above tables.

Table 10: Low voltage dual phase PDU for Oracle Flash Storage Systems

Low Voltage
kVA size
Marketing part number
Manufacturing part number
Phase
Voltage input
Number of input cords and plug type
Number of data center receptacles and
type
Maximum input current for each cord
Outlet receptacles (number/type)
Oracle FS Systems: Installation Overview
2Ph (2W + ground)
10 kVA
7104982
7051798
1 Phase
No grounded neutral conductors are
provided in the two input cords.
2x [2Ph (2W+ground)], 208Vac, 50/60 Hz,
maximum. 24A per phase
Can be connected to input sources in the
range of 200V – 240V AC (nominal)
2x NEMA L6-30P
2x NEMA L6-30R
24A
42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
24