Figure 72: Power Supply Location - Oracle FS1-2 Customer Service Manual

Flash storage system
Hide thumbs Also See for FS1-2:
Table of Contents

Advertisement

Figure 72: Power supply location

Legend
1 Power supply-1 (PS-1)
2 Power supply-0 (PS-0)
Note: To replace a power supply, you can access the faulted power supply from
the back of the Controller module. To access the power supply located in the
bottom slot (PS-0), the CMA clip must be disconnected to enable the power
supply to clear the support arm.
Note: Replacing the power supply does not require you to slide the Controller
into the extended rack position and can be performed while the Controller is in
the rack position.
Note: Ensure that the power strain relief strap on the power supply is positioned
correctly such that there is proper clearance and the power supplies can be re-
inserted into the power supply compartment without interference.
Note: Ensure that the power cable is routed correctly and there is no interference
with the Controller chassis.
Important: Do not remove the failed power supply until you have a replacement
power supply to ensure proper airflow in the Controller.
Note: For fan replacement, the Replaceable Unit list displays the names of each
fan. Each power supply contains one fan, and each fan module contains two fans.
If a fan fails in a power supply, replace the power supply. If a fan fails in a fan
module, replace the fan module. The following list identifies the names of the
fans and the corresponding customer replaceable unit (CRU).
If the following fan fails
Fan 0
Power supply 0
Controller Replacement Procedures
Replace the following CRU
103