Table 28: High Voltage Three-Phase Pdu For Oracle Flash Storage Systems - Oracle FS1-2 Customer Service Manual

Flash storage system
Hide thumbs Also See for FS1-2:
Table of Contents

Advertisement

Table 27: High voltage single phase PDU for Oracle Flash Storage Systems
(continued)
High Voltage
Maximum input current for each cord
Outlet receptacles (number/type)
Outlet groups for each PDU
PDU power cord length

Table 28: High voltage three-phase PDU for Oracle Flash Storage Systems

High Voltage
kVA size
Marketing part number
Phase
Voltage input
Number of input cords and plug type
Number of data center receptacles and
type
Maximum input current for each cord
Outlet receptacles (number/type)
Oracle FS System Hardware Specifications
1Ph (2W + ground)
25A
42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
6
2 meters (6.6 feet)
PDU power cords are 4 meters (13 feet)
long, but sections are connected for internal
routing in the rack.
3Ph (5W + ground)
15 kVA
7104980
3
[3Ph. (4W+ground)] 230/400Vac, 50/60 Hz,
maximum. 25A per phase
Can be connected to Ph-N input sources in
the range of 220V – 240V AC (nominal)
1x IEC 309, 32A (Hubbell 532P6S or
equivalent)
1x IEC 309, 32A (Hubbell 532R6S or
equivalent)
25A
42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
238