Table 27: High Voltage Single Phase Pdu For Oracle Flash Storage Systems - Oracle FS1-2 Customer Service Manual

Flash storage system
Hide thumbs Also See for FS1-2:
Table of Contents

Advertisement

Table 26: Low voltage three-phase PDU for Oracle Flash Storage Systems
(continued)
Low Voltage
Voltage input
Number of input cords and plug type
Number of data center receptacles and
type
Maximum input current for each cord
Outlet receptacles (number/type)
Outlet groups for each PDU
PDU power cord length

Table 27: High voltage single phase PDU for Oracle Flash Storage Systems

High Voltage
kVA size
Marketing part number
Phase
Voltage input
Number of input cords and plug type
Number of data center receptacles and
type
Oracle FS System Hardware Specifications
3Ph (3W + ground)
3Ph [(3W+ground)] 208Vac, 50/60 Hz,
maximum. 40A per phase
Can be connected to Ph-Ph input sources in
the range of 190V – 220V AC (nominal)
1x IEC 309, 60A (Hubbell C460P9W or
equivalent)
1x IEC 309, 60A (Hubbell 460R9S or
equivalent)
40A
42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
6
2 meters (6.6 feet)
PDU power cords are 4 meters (13 feet)
long, but sections are connected for internal
routing in the rack.
1Ph (2W + ground)
10 kVA
7104983
1
2x [2Ph. (2W+ground)] 230Vac, 50 Hz,
maximum. 25A per phase
Can be connected to Ph-N input sources in
the range of 220V – 240V AC (nominal)
2x IEC 309, 32A (Hubbell 332P6S or
equivalent)
2x IEC 309, 32A (Hubbell 332R6S or
equivalent)
237