B.16 Control Mode Dependent Parameter Default Values
B.16 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2). Changing
the control mode initializes these parameters to the values shown here.
u

A1-02 (Motor 1 Control Mode) Dependent Parameters

Table B.2 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
No.
Name
b2-01
DC Injection Braking Start Frequency
b2-04
DC Injection Braking Time at Stop
b3-01
Speed Search Selection at Start
b3-02
Speed Search Deactivation Current
b3-14
Bi-Directional Speed Search Selection
b8-01
Energy Saving Control Selection
b8-02
Energy Saving Gain
b8-03
Energy Saving Control Filter Time Constant
C2-01
S-Curve Time at Acceleration Start
C3-01
Slip Compensation Gain
C3-02
Slip Compensation Primary Delay Time
C4-01
Torque Compensation Gain
C4-02
Torque Compensation Primary Delay Time
C5-01
ASR Proportional Gain 1
C5-02
ASR Integral Time 1
C5-03
ASR Proportional Gain 2
C5-04
ASR Integral Time 2
C5-06
ASR Primary Delay Time Constant
C6-02
Carrier Frequency Selection
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-07
Middle Output Frequency
E1-08
Middle Output Frequency Voltage
E1-09
Minimum Output Frequency
E1-10
Minimum Output Frequency Voltage
F1-01
PG 1 Pulses Per Revolution
F1-05
PG 1 Rotation Selection
F1-09
Overspeed Detection Delay Time
L1-01
Motor Overload Protection Selection
L3-20
DC Bus Voltage Adjustment Gain
L3-21
Accel/Decel Rate Calculation Gain
L4-02
Speed Agreement Detection Width
L4-04
Speed Agreement Detection Width (+/-)
L8-38
Carrier Frequency Reduction Selection
Carrier Frequency Reduction Off Delay
L8-40
Time
o1-03
Digital Operator Display Selection
o1-04
V/f Pattern Display Unit
<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
456
Setting Range
Resolution
0.0 to 10.0
0.1 Hz
0.00 to 10.00
0.01 s
0 to 1
0 to 200
1%
0 to 1
1
0 to 1
0.0 to 10.0
0.1
0.00 to 10.00
0.01 s
0.00 to 10.00
0.01 s
0.0 to 2.5
0.1
0 to 10000
1 ms
0.00 to 2.50
0.01
0 to 10000
1 ms
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.000 to 0.500
0.001 s
1 to F
40.0 to 400.0
0.1 Hz
0.0 to 733.1
0.1 V
0.0 to 400.0
0.1 Hz
0.0 to 400.0
0.1 Hz
0.0 to 733.1
0.1 V
0.0 to 400.0
0.1 Hz
0.0 to 733.1
0.1 V
0 to 60000
1 ppr
0 to 1
0.0 to 2.0
0.1 s
0 to 4
0.00 to 5.00
0.01
0.00 to 10.00
0.01
0.0 to 20.0
0.1 Hz
0.0 to 20.0
0.1 Hz
0 to 2
1
0.00 to 2.00
0.01 s
0 to 3
1
0 to 1
1
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Control Modes (A1-02)
V/f (0)
V/f w/PG (1)
OLV (2)
0.5
0.5
0.5
0.50
0.50
0.50
0
1
120
100
1
0
0
0
0.7
0.50
2.00 (Motor
Capacity: 55
kW and
above)
0.20
0.20
0.20
0.0
1.0
2000
200
1.00
1.00
1.00
200
200
20
0.20
0.200
0.02
0.050
<1>
<1>
7
7
7
60.0
60.0
60.0
575
575
575
60.0
60.0
60.0
3.0
3.0
3.0
15.0
15.0
15.0
1.5
1.5
0.5
9.0
9.0
2.0
600
600
600
0
0
1.0
1
1
1.00
1.00
0.30
1.00
1.00
1.00
2.0
2.0
2.0
2.0
2.0
2.0
<1>
<1>
<1>
0.50
0.50
0.50
0
0
CLV (3)
0.5
0.50
0
1
1
1
0
0
1.0
0.01
0.05 (Motor
Capacity: 55
kW and
above)
0.20
1.0
20.00
0.500
20.00
0.500
0.004
<1>
<1>
7
60.0
575
60.0
3.0
15.0
0.0
0.0
600
0
0
0.0
1
1
0.30
1.00
2.0
2.0
<1>
0.50
0
0
0