H5: Memobus/Modbus Serial Communication - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-07
Output Terminal FM Signal
(423)
Level Selection
Multi-Function Analog
H4-08
Output Terminal AM Signal
(424)
Level Selection
u

H5: MEMOBUS/Modbus Serial Communication

No.
(Addr.
Name
Hex)
H5-01
(425)
Drive Node Address
<1>
H5-02
Communication Speed
(426)
Selection
H5-03
Communication Parity
(427)
Selection
H5-04
Stopping Method after
(428)
Communication Error (CE)
H5-05
Communication Fault
(429)
Detection Selection
H5-06
Drive Transmit Wait Time
(42A)
H5-07
RTS Control Selection
(42B)
H5-09
CE Detection Time
(435)
Unit Selection for
H5-10
MEMOBUS/Modbus
(436)
Register 0025H
H5-11
Communications ENTER
(43C)
Function Selection
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Description
All Modes
Selects drive station node number (address) for MEMOBUS/Modbus
terminals R+, R-, S+, S-. Cycle power for the setting to take effect.
All Modes
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
All Modes
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
All Modes
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
All Modes
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault
will occur.
All Modes
Set the wait time between receiving and sending data.
All Modes
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
All Modes
Sets the time required to detect a communications error.
Adjustment may be needed when networking several drives.
All Modes
0: 0.1 V units
1: 1 V units
All Modes
0: Drive requires an Enter command before accepting any changes to
parameter settings.
1: Parameter changes are activated immediately without the Enter command
(same as V7).
B.9 H Parameters: Multi-Function Terminals
Values
Page
Default: 0
235
Range: 0 to 2
Default: 0
235
Range: 0 to 2
Values
Page
Default: 1F (Hex)
Min.: 0
468
Max.: FF
Default: 3
468
Range: 0 to 8
Default: 0
468
Range: 0 to 2
Default: 0
468
Range: 0 to 3
Default: 0
469
Range: 0, 1
Default: 5 ms
Min.: 5
469
Max.: 65
Default: 1
469
Range: 0, 1
Default: 2.0 s
Min.: 0.0
469
Max.: 10.0
Default: 0
469
Range: 0, 1
Default: 1
470
Range: 0, 1
425