Table B.3 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
No.
Name
b2-01
DC Injection Braking Start Frequency
b2-04
DC Injection Braking Time at Stop
b3-01
Speed Search Selection at Start
b3-02
Speed Search Deactivation Current
b3-14
Bi-Directional Speed Search Selection
b8-01
Energy Saving Control Selection
b8-02
Energy Saving Gain
b8-03
Energy Saving Control Filter Time Constant
C2-01
S-Curve Time at Acceleration Start
C3-01
Slip Compensation Gain
C3-02
Slip Compensation Primary Delay Time
C4-01
Torque Compensation Gain
C4-02
Torque Compensation Primary Delay Time
C5-01
ASR Proportional Gain 1
C5-02
ASR Integral Time 1
C5-03
ASR Proportional Gain 2
C5-04
ASR Integral Time 2
C5-06
ASR Primary Delay Time Constant
C6-02
Carrier Frequency Selection
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-07
Middle Output Frequency
E1-08
Middle Output Frequency Voltage
E1-09
Minimum Output Frequency
E1-10
Minimum Output Frequency Voltage
F1-01
PG 1 Pulses Per Revolution
F1-05
PG 1 Rotation Selection
F1-09
Overspeed Detection Delay Time
L1-01
Motor Overload Protection Selection
L3-20
DC Bus Voltage Adjustment Gain
L3-21
Accel/Decel Rate Calculation Gain
L4-02
Speed Agreement Detection Width
L4-04
Speed Agreement Detection Width (+/-)
L8-38
Carrier Frequency Reduction Selection
Carrier Frequency Reduction Off Delay
L8-40
Time
o1-03
Digital Operator Display Selection
o1-04
V/f Pattern Display Unit
<1> Value calculated as a percentage of the maximum output frequency.
<2> Default setting is dependent on parameter E5-01, Motor Code Selection.
<99> PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
B.16 Control Mode Dependent Parameter Default Values
Setting Range
Resolution
0.0 to 10.0
0.1 Hz
0.00 to 10.00
0.01 s
0 to 1
0 to 200
1%
0 to 1
1
0 to 1
0.0 to 10.0
0.1
0.00 to 10.00
0.01 s
0.00 to 10.00
0.01 s
0.0 to 2.5
0.1
0 to 10000
1 ms
0.00 to 2.50
0.01
0 to 10000
1 ms
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.000 to 0.500
0.001 s
1 to F
40.0 to 400.0
0.1 Hz
0.0 to 733.1
0.1 V
0.0 to 400.0
0.1 Hz
0.0 to 400.0
0.1 Hz
0.0 to 733.1
0.1 V
0.0 to 400.0
0.1 Hz
0.0 to 733.1
0.1 V
0 to 60000
1 ppr
0 to 1
0.0 to 2.0
0.1 s
0 to 4
0.00 to 5.00
0.01
0.00 to 10.00
0.01
0.0 to 20.0
0.1 Hz
0.0 to 20.0
0.1 Hz
0 to 2
1
0.00 to 2.00
0.01 s
0 to 3
1
0 to 1
1
Control Modes (A1-02)
AOLV/PM (6)
<99>
OLV/PM (5)
<99>
<1>
0.5 Hz
1.0%
0.00
0.00
0
0
1
1
1
1.00
1.00
0.00
0.00
100
100
2
2
<2>
<2>
<2>
<2>
<2>
<2>
1024
1024
1
1
4
4
0.65
0.65
2.50
2.50
<1>
2.0 Hz
4.0%
<1>
2.0 Hz
4.0%
0
0
0.00
0.00
0
1
1
<99>
CLV/PM (7)
<1>
0.5%
0.00
1
1
1
1.00
0.00
100
2
<2>
<2>
<2>
1024
1
4
0.65
2.50
<1>
4.0%
<1>
4.0%
0
0.00
1
1
B
457