Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID
control, the Dwell function, Energy Savings, and a variety of other application-related settings.
u

b1: Operation Mode Selection

OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
No.
(Addr.
Name
Hex)
b1-01
Frequency Reference
(180)
Selection 1
b1-02
Run Command
(181)
Selection 1
b1-03
Stopping Method Selection
(182)
b1-04
Reverse Operation Selection
(183)
b1-05
Action Selection below
(184)
Minimum Output Frequency
b1-06
Digital Input Reading
(185)
b1-07
LOCAL/REMOTE Run
(186)
Selection
b1-08
Run Command Selection in
(187)
Programming Mode
b1-14
Phase Order Selection
(1C3)
b1-15
Frequency Reference
(1C4)
Selection 2
384
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
All Modes
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)
All Modes
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
All Modes
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
All Modes
0: Reverse enabled.
1: Reverse disabled.
V/f
V/f w PG
OLV/PM
AOLV/PM
0: Operates according to frequency reference (E1-09 is disabled).
1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).
All Modes
0: Input status is read once and processed immediately (for quicker response)
1: Input is read twice and processed only if the status is the same in both
readings (robust against noisy signals)
All Modes
0: An external Run command must be cycled at the new source in order to be
activated.
1: An external Run command at the new source is accepted immediately.
All Modes
0: Run command is not accepted while in Programming Mode.
1: Run command is accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.
V/f
V/f w PG
OLV/PM
AOLV/PM
0: Standard
1: Switch phase order (reverses the direction of the motor)
All Modes
Enabled when an input terminal set for "External reference" (H1-oo = 2)
closes.
0: Digital operator
1: Terminals (analog input terminals)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Values
Page
Default: 1
126
Range: 0 to 4
Default: 1
127
Range: 0 to 3
Default: 0
128
<1>
Range: 0 to 3
Default: 0
130
Range: 0, 1
Default: 0
130
Range: 0 to 3
Default: 1
131
Range: 0, 1
Default: 0
132
Range: 0, 1
Default: 0
132
Range: 0 to 2
Default: 0
132
Range: 0, 1
Default: 0
132
Range: 0 to 4