B: Application; B: Application; B1: Operation Mode Selection - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

5.2 b: Application

5.2

b: Application

u

b1: Operation Mode Selection

n
b1-01: Frequency Reference Selection 1
Selects the frequency reference source 1 for the REMOTE mode.
Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED
on the digital operator will light and the STOP indicator will flash.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
No.
b1-01
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-oo parameters.
• entering the frequency reference on the operator keypad.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in
used.
Table 5.5 Analog Input Settings for Frequency Reference Using Voltage Signals
Terminal
Signal Level
0 to 10 Vdc
A1
-10 to +10 Vdc
0 to 10 Vdc
A2
-10 to +10 Vdc
0 to 10 Vdc
A3
-10 to +10 Vdc
2 k
Figure 5.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Use the wiring example shown in
S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to
126
Parameter Name
Frequency Reference Selection 1
Signal Level
Function Selection
Selection
H3-01 = 0
H3-02 = 0
(Frequency Reference
H3-01 = 1
H3-09 = 0
H3-10 = 0
(Frequency Reference
H3-09 = 1
H3-05 = 0
H3-06 = 0
(Frequency Reference
H3-05 = 1
Drive
+V
10.5 V, 20 mA power supply
0 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
-V
-10.5 V, 20 mA power supply
Figure 5.1
for any other analog input terminals. When using input A2 make sure DIP switch
Parameter Settings
Gain
H3-03
Bias)
H3-11
Bias)
H3-07
Bias)
-10 to 10 V
4 k
Table 5.6
to set terminal A2 for current input.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Setting Range
0 to 4
Table 5.5
Notes
Bias
H3-04
Set DIP switch S1 on the terminal
H3-12
board to "V" for voltage input.
H3-08
-
Drive
+V
10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
-V
-10.5 V, 20 mA power supply
Default
1
for the input
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents