Setting 2: Drive dedicated motor (speed range for constant torque: 1:10)
Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will allow
the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger an overload
fault.
Overload Tolerance
150
Rated Speed=100% Speed
60 s
A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
100
C: Max. speed for 132MJ and below
55
50
A
Continuous
B
0
110
100120 167 200
Speed (%)
Setting 3: Vector motor (speed range for constant torque: 1:100)
Use this setting when operating a drive-dedicated motor that allows constant torque in a speed range of 1:100. This motor type
is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload
fault.
Overload Tolerance
150
Rated Speed=100% Speed
60 s
A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below
100
90
Continuous
50
A
B
0 1
100120 167 200
Speed (%)
Setting 4: PM derated torque motor
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Use this setting when operating a PM motor. PM motors for derated torque have a self-cooling design and the overload tolerance
drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload characteristics,
providing overheat protection across the entire speed range.
Overload Tolerance
150
120
100
80
50
0.0
10
33
Motor Speed (%)
Setting 5: Constant torque PM motors (constant torque range of 1:500)
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Sets necessary protection characteristics when driving a PM with constant torque. These motors allow for a speed control from
0.2% to 100% when operating with 100% load. Slower speeds with 100% load will trigger overload.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Motor is designed to effectively cool
itself even at low speeds.
C
Motor is designed to effectively cool
itself at speeds near 0.6 Hz.
C
60 s
Motor is designed to produce 100%
Continuous
torque at base speed. Built with
effective cooling capabilities.
100
Cooling Ability
Cooling Ability
Cooling Ability
5.8 L: Protection Functions
Overload Characteristics
Continuous operation with 100% load
from 6 Hz to E1-06, Motor Base
Frequency.
Overload Characteristics
Continuous operation with 100% load
from 0.6 Hz to E1-06, Motor Base
Frequency.
Overload Characteristics
Reaching 100% when operating at
below the base frequency causes a
motor overload fault (oL1). The drive
fault output closes and the motor coasts
to stop.
5
239