Terminal Configuration - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

n
Serial Communication Terminals
Type
No.
R+
R-
MEMOBUS/Modbus
S+
<1>
Communication
S-
IG
<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position.
I/O Connections on page 68
u

Terminal Configuration

The control circuit terminals are arranged as shown in
n
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
ends. Refer to
Table 3.8
for ferrule terminal types and sizes.
Screw
Terminal
Size
S1-S8, SC, SP, SN,
RP, V+, V-, A1, A2,
A3, AC, M1-M6,
MA, MB, MC, MP,
M3
AM, FM, AC, S+,
S-, R+, R-, IG, HC,
H1, H2, DM+, DM-
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Table 3.6 Control Circuit Terminals: Serial Communications
Signal Name
Communications input (+)
Communications input (-)
Communications output (+)
Communications output (-)
Shield ground
for more information on the termination resistor.
Figure
E(G) HC H1 H2 DM+ DM- IG R+ R- S+ S-
Figure 3.15 Control Circuit Terminal Arrangement
Table
3.7. For simpler and more reliable wiring, use crimp ferrules on the wire
Table 3.7 Wire Gauges
Bare Wire Terminal
Tightening
Torque
Applicable
N•m
wire size
(lb. in)
2
mm
Stranded wire:
0.2 to 1.0
0.5 to 0.6
(24 to 16)
(4.4 to 5.3)
Solid wire:
0.2 to 1.5
(24 to 16)
MEMOBUS/Modbus communication: Use an
RS-485 or RS-422 cable to connect the drive.
3.15.
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
Recomm.
Applicable
wire size
2
(AWG)
mm
(AWG)
mm
0.25 to 0.5
0.75 (18)
3.9 Control Circuit Wiring
Function (Signal Level)
RS-485/422
MEMOBUS/Modbus
communication
protocol
115.2 kbps (max.)
0 V
M3 M6 M4
M1 M2 M5
MA MB MC
Ferrule-Type Terminal
Recomm.
wire size
wire size
2
2
(AWG)
mm
(AWG)
0.5 (20)
(24 to 20)
Refer to Control
3
Wire Type
Shielded wire,
etc.
63