D2: Frequency Upper/Lower Limits; D3: Jump Frequency - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

B.6 d: References
No.
(Addr.
Name
Hex)
d1-14
(28F)
Frequency Reference 14
d1-15
(290)
Frequency Reference 15
d1-16
(291)
Frequency Reference 16
d1-17
(292)
Jog Frequency Reference
<1> Range upper limit is determined by the maximum output frequency (E1-04) and the upper limit of the frequency reference (d2-01).
<2> The setting range is 0.0 to 66.0 in AOLV/PM.
u

d2: Frequency Upper/Lower Limits

No.
(Addr.
Name
Hex.)
d2-01
Frequency Reference Upper
(289)
Limit
d2-02
Frequency Reference Lower
(28A)
Limit
d2-03
Master Speed Reference
(293)
Lower Limit
u

d3: Jump Frequency

No.
(Addr.
Name
Hex)
d3-01
Jump Frequency 1
(294)
d3-02
Jump Frequency 2
(295)
d3-03
Jump Frequency 3
(296)
398
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Sets the Jog frequency reference. Setting units are determined by parameter
o1-03.
All Modes
Sets the frequency reference upper limit as a percentage of the maximum
output frequency.
All Modes
Sets the frequency reference lower limit as a percentage of the maximum
output frequency.
All Modes
Sets the lower limit for frequency references from analog inputs as a
percentage of the maximum output frequency.
All Modes
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
All Modes
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
All Modes
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
Description
Description
Values
Page
Default: 0.00 Hz
Min.: 0.00
169
<1>
Max.: 400.00
<2>
Default: 0.00 Hz
Min.: 0.00
169
<1>
Max.: 400.00
<2>
Default: 0.00 Hz
Min.: 0.00
169
<1>
Max.: 400.00
<2>
Default: 6.00 Hz
Min.: 0.00
169
<1>
Max.: 400.00
<2>
Setting
Page
Default: 100.0%
Min.: 0.0
171
Max.: 110.0
Default: 0.0%
Min.: 0.0
171
Max.: 110.0
Default: 0.0%
Min.: 0.0
172
Max.: 110.0
Values
Page
Default: 0.0 Hz
Min.: 0.0
172
Max.: 400.0
Default: 0.0 Hz
Min.: 0.0
172
Max.: 400.0
Default: 0.0 Hz
Min.: 0.0
172
Max.: 400.0