Standard Connection Diagram; Standard Connection Diagram - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

3.2 Standard Connection Diagram

3.2

Standard Connection Diagram

Connect the drive and peripheral devices as shown in
Figure
3.1. It is possible to set and run the drive via the digital operator
without connecting digital I/O wiring. This section does not discuss drive operation;
Refer to Start-Up Programming &
Operation on page 77
for instructions on operating the drive.
NOTICE: Inadequate wiring could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable codes.
The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical amperes, 600 Vac maximum (600 V Class).
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the motor
insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.
NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
NOTICE: The minimum load for the relay outputs M1-M2, M3-M4, M5-M6, and MA-MB-MC is 10 mA.
50
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents