B3: Speed Search - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

B.4 b: Application
u

b3: Speed Search

OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
No.
(Addr
Name
Hex.)
b3-01
Speed Search Selection at
(191)
Start
b3-02
Speed Search Deactivation
(192)
Current
b3-03
Speed Search Deceleration
(193)
Time
b3-04
V/f Gain during Speed
(194)
Search
b3-05
Speed Search Delay Time
(195)
b3-06
Output Current 1 during
(196)
Speed Search
b3-10
Speed Search Detection
(19A)
Compensation Gain
b3-14
Bi-Directional Speed Search
(19E)
Selection
b3-17
Speed Search Restart
(1F0)
Current Level
b3-18
Speed Search Restart
(1F1)
Detection Time
b3-19
Number of Speed Search
(1F2)
Restarts
b3-24
Speed Search Method
(1C0)
Selection
b3-25
Speed Search Wait Time
(1C8)
<1> Default setting is determined by parameter A1-02, Control Mode Setting.
386
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
V/f
V/f w PG
OLV/PM
AOLV/PM
0: Disabled
1: Enabled
V/f
V/f
V/f w PG
OLV/PM
AOLV/PM
Sets the current level at which the speed is assumed to be detected and Speed
Search is ended. Set as a percentage of the drive rated current.
V/f
V/f
V/f w PG
OLV/PM
AOLV/PM
Sets output frequency reduction time during Speed Search.
V/f
V/f
V/f w PG
V/f w PG
OLV/PM
AOLV/PM
Determines how much to lower the V/f ratio during Speed Search.
Output voltage during Speed Search equals the V/f setting multiplied by b3-04.
All Modes
When using an external contactor on the output side, b3-05 delays executing
Speed Search after a momentary power loss to allow time for the contactor to
close.
V/f
V/f
V/f w PG
V/f w PG
OLV/PM
AOLV/PM
Sets the current injected to the motor at the beginning of Speed Estimation
Speed Search. Set as a coefficient for the motor rated current.
V/f
V/f
V/f w PG
OLV/PM
AOLV/PM
Sets the gain which is applied to the speed detected by Speed Estimation Speed
Search before the motor is reaccelerated. Increase this setting if ov occurs
when performing Speed Search after a relatively long period of baseblock.
V/f
V/f
V/f w PG
V/f w PG
OLV/PM
AOLV/PM
0: Disabled (uses the direction of the frequency reference)
1: Enabled (drive detects which way the motor is rotating)
V/f
V/f
V/f w PG
OLV/PM
AOLV/PM
Sets the Speed Search restart current level as a percentage of the drive rated
current.
V/f
V/f
V/f w PG
OLV/PM
AOLV/PM
Sets the time to detect Speed Search restart.
V/f
V/f
V/f w PG
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
Sets the number of times the drive can attempt to restart when performing
Speed Search.
V/f
V/f
V/f w PG
V/f w PG
OLV/PM
AOLV/PM
0: Current Detection
1: Speed Estimation
V/f
V/f
V/f w PG
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
Sets the time the drive must wait between each Speed Search restart attempt.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
OLV
OLV
CLV
CLV/PM
Values
Page
<1>
Default:
138
Range: 0, 1
<1>
Default:
139
Min.: 0%
Max.: 200%
Default: 2.0 s
Min.: 0.1
139
Max.: 10.0
<2>
Default:
139
Min.: 10%
Max.: 100%
Default: 0.2 s
Min.: 0.0
139
Max.: 100.0
<2>
Default:
139
Min.: 0.0
Max.: 2.0
Default: 1.05
Min.: 1.00
139
Max.: 1.20
<1>
Default:
139
Range: 0, 1
Default: 150%
Min.: 0
140
Max.: 200
Default: 0.10 s
Min.: 0.00
140
Max.: 1.00
Default: 3
Min.: 0
140
Max.: 10
Default: 0
140
Range: 0, 1
Default: 0.5 s
Min.: 0.0
140
Max.: 30.0

Hide quick links: