4.3 The Drive and Programming Modes
u

Simplified Setup Using the Setup Group

The Setup Group lists the basic parameters necessary to set up the drive for an application. This group expedites the startup
process for an application by showing only the most important parameters for the application.
n
Using the Setup Group
Figure 4.7
illustrates how to enter and how to change parameters in the Setup Group.
The first display shown when entering the Setup Group is the Application Selection menu. Skipping this display will keep the
current Setup Group parameter selection. The default setting for the Setup Group is a group of parameters most commonly
use in general-purpose applications. Pressing the ENTER key from the Application Selection menu and selecting an
Application Preset will change the Setup Group to parameters optimal for the application selected.
Selection on page
97.
In this example, the Setup Group is accessed to change b1-01 from 1 to 0. This changes the source of the frequency reference
from the control circuit terminals to the digital operator.
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00 A
LREF
JOG
FWD
FWD/REV
Frequency reference
appears when
powered up
<1> Use the up and down arrow keys to scroll through the Setup Group. Press the ENTER key to view or change parameter settings.
<2> To return to the previous menu without saving changes, press the ESC key.
88
- MODE -
PRG
Quick Setting
HELP
FWD
DATA
<1>
- SETUP -
PRG
Application Sel
A1-06= 0
*0*
General
Home
FWD
Parameter Display
- SETUP -
PRG
Control Method
A1-02= 2
*2*
Open Loop Vector
Home
FWD
- SETUP -
PRG
Ref Source 1
b1-01= 1
*1*
Analog Input
Home
FWD
- SETUP -
PRG
Run Source 1
b1-02= 1
*1*
Digital Inputs
Home
FWD
- SETUP -
PRG
StallP Decel Sel
L3-04= 1
*1*
General Purpose
Home
FWD
Figure 4.7 Setup Group Example
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Rdy
DATA
Rdy
DATA
Rdy
DATA
Entry Accepted
Rdy
DATA
Rdy
DATA
Refer to Application
- SETUP -
PRG
Rdy
Ref Source 1
b1-01=
1
*1*
Analog Input
"1"
FWD
Control Circuit
Terminal
<2>
- SETUP -
PRG
Ref Source 1
b1-01=
0
*1*
Operator
"1"
FWD
Operator
<2>
Rdy