B.12 o: Operator-Related Settings
B.12 o: Operator-Related Settings
The o parameters set up the digital operator displays.
u

o1: Digital Operator Display Selection

OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
No.
(Addr.
Name
Hex)
o1-01
Drive Mode Unit Monitor
(500)
Selection
o1-02
User Monitor Selection after
(501)
Power Up
o1-03
Digital Operator Display
(502)
Selection
o1-04
V/f Pattern Display Unit
(503)
o1-10
User-Set Display Units
(520)
Maximum Value
o1-11
User-Set Display Units
(521)
Decimal Display
<1> Default setting is dependent on parameter A1-02, Control Mode Selection.
<2> Default setting is dependent on parameter o1-03, Digital Operator Display Selection.
u

o2: Digital Operator Keypad Functions

No.
(Addr.
Name
Hex)
o2-01
LO/RE Key Function
(505)
Selection
o2-02
STOP Key Function
(506)
Selection
o2-03
User Parameter Default
(507)
Value
o2-04
Drive Model Selection
(508)
440
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
All Modes
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: Uo-oo.
All Modes
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
All Modes
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
V/f
V/f w PG
OLV/PM
AOLV/PM
AOLV/PM
0: Hz
1: r/min
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
All Modes
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
All Modes
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
All Modes
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
All Modes
Enter the drive model. Setting required only if installing a new control board.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
OLV
CLV
CLV
CLV/PM
CLV/PM
Description
Values
Page
Default: 106
(Monitor U1-06)
278
Range: 104 to 809
Default: 1
278
Range: 1 to 5
<1>
Default:
278
Range: 0 to 3
<1>
Default:
279
Range: 0, 1
<2>
Default:
279
Range: 1 to 60000
<2>
Default:
279
Range: 0 to 3
Values
Page
Default: 1
279
Range: 0, 1
Default: 1
280
Range: 0, 1
Default: 0
280
Range: 0 to 2
Default:
Determined by
280
drive capacity