5.6 F: Option Settings
No.
F6-59
F6-60
F6-61
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value × 2
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 × 2
n
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the heartbeat function.
No.
F6-62
n
F6-63: DeviceNet Network MAC ID
Displays the MAC ID assigned to the drive. F6-63 is used only as a monitor.
No.
F6-63
n
F6-64 to F6-71: Dynamic Assembly Parameters (Reserved)
206
Parameter Name
DeviceNet Power Scaling
DeviceNet Voltage Scaling
DeviceNet Time Scaling
Scaling
6
= 32000.
Parameter Name
DeviceNet Heartbeat Interval
Parameter Name
DeviceNet Network MAC ID
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Setting Range
-15 to 15
-15 to 15
-15 to 15
Setting Range
0 to 10
Setting Range
0 to 63 (read only)
Default
0
0
0
Default
0
Default
0