B.4 Control Mode Dependent Parameter Default Values
B.4 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2).
These parameters are initialized to the shown values if the control mode is changed.
Table B.1 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
Parameter
b2-03
DC Injection Braking Time at Start
b2-04
DC Injection Braking Time at Stop
b3-02
Speed Search Deactivation Current
C2-01
S-Curve Characteristic at Accel Start
C3-01
Slip Compensation Gain
C3-02
Slip Compensation Primary Delay Time
C4-01
Torque Compensation Gain
C4-02
Torque Compensation Primary Delay Time
C6-02
Carrier Frequency Selection
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-07
Middle Output Frequency
E1-08
Middle Output Frequency Voltage
E1-09
Minimum Output Frequency
E1-10
Minimum Output Frequency Voltage
E1-11
Middle Output Frequency 2
E1-12
Mid Output Frequency Voltage 2
E1-13
Base Voltage
L1-01
Motor Overload Protection Selection
L8-18
Software Current Limit Selection
S6-04
Main Circuit Voltage Adjustment Gain
S6-05
Accel/Decel Calculation Gain
<9> Default setting is determined by the motor code set to parameter E5-01.
<11> Default setting is determined by the drive model selection set in parameter o2-04.
<17> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Table B.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
Parameter
E3-04
Motor 2 Max Output Frequency
E3-05
Motor 2 Max Voltage
E3-06
Motor 2 Base Frequency
E3-07
Motor 2 Mid Output Frequency
E3-08
Motor 2 Mid Output Frequency Voltage
E3-09
Motor 2 Minimum Output Frequency
E3-10
Motor 2 Minimum Output Frequency Voltage
E3-11
Motor 2 Mid Output Frequency 2
E3-12
Motor 2 Mid Output Frequency Voltage 2
E3-13
Motor 2 Base Voltage
E4-14
Motor 2 Slip Compensation Gain
<17> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Note: Motor 2 cannot be a PM motor.
364
Description
<17>
<17>
<17>
<17>
<17>
Description
<17>
<17>
<17>
<17>
Setting Range
Resolution
0.00 to 10.00
0.00 to 10.00
0 to 200
0.00 to 10.00
0.0 to 2.5
0 to 10000
0.00 to 2.50
0 to 10000
1 to 6, F
40.0 to 400.0
0.0 to 255.0
0.0 to 400.0
0.0 to 400.0
0.0 to 255.0
0.0 to 400.0
0.0 to 255.0
0.0 to 400.0
0.0 to 255.0
0.0 to 255.0
0 to 4
0, 1
0.00 to 5.00
0.00 to 200.00
Setting Range
40.0 to 400.0
0.0 to 255.0
0.0 to 400.0
0.0 to 400.0
0.0 to 255.0
0.0 to 400.0
0.0 to 255.0
<17>
0.0 to 400.0
0.0 to 255.0
0.0 to 255.0
0.0 to 2.5
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Control Modes (A1-02)
V/f (0)
OLV (2)
0.01 s
0.00
0.01 s
0.50
1%
120
0.01 s
0.20
0.1
0.0
1 ms
2000
0.01
1.00
1 ms
200
1
<11>
0.1 Hz
50.0
0.1 V
200.0
0.1 Hz
50.0
0.1 Hz
2.5
0.1 V
16.0
0.1 Hz
1.3
0.1 V
12.0
0.1 Hz
0.0
0.1 V
0.0
0.1 V
0.0
-
1
1
1
0.01
1.00
0.01
1.00
Control Modes (E3-01)
Resolution
V/f (0)
0.1 Hz
50.0
0.1 V
200.0
0.1 Hz
50.0
0.1 Hz
2.5
0.1 V
16.0
0.1 Hz
1.3
0.1 V
12.0
0.1 Hz
0.0
0.1 V
0.0
0.1 V
0.0
0.1
0.0
PM (5)
0.00
0.50
0.00
100
0.20
1.00
1.0
200
1.00
0.00
20
100
2
<11>
50.0
<9>
200.0
<9>
50.0
<9>
3.0
12.0
0.5
<9>
3.0
0.0
0.0
0.0
1
4
1
0.30
0.65
1.00
2.50
OLV (2)
50.0
200.0
50.0
3.0
14.4
0.5
2.5
0.0
0.0
0.0
1.0