H3: Multi-Function Analog Inputs - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

B.9 H Parameters: Multi-Function Terminals
H2-oo
Function
Setting
DriveWorksEZ
90 to 92
digital outputs 1 to 3
100 to 192 Function 0 to 92 with inverse
output
u

H3: Multi-Function Analog Inputs

No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal Level
(410)
Selection
H3-02
Terminal A1 Function
(434)
Selection
H3-03
(411)
Terminal A1 Gain Setting
H3-04
(412)
Terminal A1 Bias Setting
H3-05
Terminal A3 Signal Level
(413)
Selection
H3-06
Terminal A3 Function
(414)
Selection
H3-07
(415)
Terminal A3 Gain Setting
H3-08
(416)
Terminal A3 Bias Setting
H3-09
Terminal A2 Signal Level
(417)
Selection
H3-10
Terminal A2 Function
(418)
Selection
H3-11
(419)
Terminal A2 Gain Setting
H3-12
(41A)
Terminal A2 Bias Setting
H3-13
Analog Input Filter Time
(41B)
Constant
422
H2 Multi-Function Digital Output Settings
All Modes
Reserved for DWEZ digital output functions.
All Modes
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the function of terminal A1.
All Modes
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
All Modes
Sets the level of the input value selected in H3-02 when 0 V is input at terminal
A1.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the function of terminal A3.
All Modes
Sets the level of the input value selected in H3-06 when 10 V is input at
terminal A3.
All Modes
Sets the level of the input value selected in H3-06 when 0 V is input at terminal
A3.
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage
input signal.
All Modes
Sets the function of terminal A2.
All Modes
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input
at terminal A2.
All Modes
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.
All Modes
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used
for noise filtering.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
Description
Page
227
227
Values
Page
Default: 0
228
Range: 0, 1
Default: 0
228
Range: 0 to 31
Default: 100.0%
Min.: -999.9
228
Max.: 999.9
Default: 0.0%
Min.: -999.9
228
Max.: 999.9
Default: 0
229
Range: 0, 1
Default: 2
229
Range: 0 to 31
Default: 100.0%
Min.: -999.9
229
Max.: 999.9
Default: 0.0%
Min.: -999.9
229
Max.: 999.9
Default: 2
230
Range: 0 to 3
Default: 0
230
Range: 0 to 31
Default: 100.0%
Min.: -999.9
230
Max.: 999.9
Default: 0.0%
Min.: -999.9
230
Max.: 999.9
Default: 0.03 s
Min.: 0.00
230
Max.: 2.00