Fine-Tuning Open Loop Vector Control

Problem
Parameter No.
• Poor motor torque
and speed response
AFR Gain
• Motor hunting and
(n2-01)
oscillation at speeds
between 10 and 40 Hz
• Poor motor torque
and speed response
AFR Time Constant 1
• Motor hunting and
(n2-02)
oscillation at speeds
between 10 and 40 Hz
AFR Time Constant 2
(n2-03)
Overvoltage trips when
accelerating,
decelerating, or during
sudden speed or load
changes
Torque Compensation
Primary Delay Time
Constant 2 (C4-06)
• Poor motor torque
Torque Compensation
and speed response
Primary Delay Time
• Motor hunting and
Constant 1 (C4-02)
oscillation
Slip Compensation
Poor speed response
Primary Delay Time
and stability
Constant (C3-02)
Slip Compensation Gain
Poor speed precision
(C3-01)
Poor speed precision
Slip Compensation
during regenerative
Selection During
operation
Regeneration (C3-04)
• Motor noise
Carrier Frequency
• Motor hunting and
Selection (C6-02)
oscillation occur at
speeds below 10 Hz
• Poor motor torque at
Mid Output Voltage A
low speeds
(E1-08)
• Poor speed response
Minimum Output
• Motor instability at
Voltage (E1-10)
start
<1> Default setting value is dependent on parameter A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<2> Default settings change after changing the control method (A1-02) or selecting a different V/f pattern (E1-03).
When using OLV, leave the torque compensation gain (C4-01) at its default setting of 1.00.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Table 6.2 Parameters for Fine-Tuning Performance in OLV
• Gradually reduce the setting in 0.05 increments if motor torque
and speed response are too slow.
• Gradually increase the setting in 0.05 increments if motor hunting
and oscillation occur.
• Gradually reduce the setting in 10 ms increments and check the
performance to improve motor torque speed response.
• Gradually increase the setting by 50 ms increments and check the
performance if motor hunting and oscillation occur as a result of
load inertia.
Note: Ensure that n2-02 ≤ n2-03. When changing n2-02, set
C4-02 (Torque Compensation Primary Delay Time
Constant 1) accordingly.
• Gradually increase the setting in 50 ms increments if overvoltage
occurs.
• Gradually reduce the setting in 10 ms increments if response is
slow.
Note: Ensure that n2-02 ≤ n2-03. When making adjustments to
n2-03, increase the value of C4-06 (Torque
Compensation Primary Delay Time 2) proportionally.
• Gradually increase the setting in 10 ms increments and check the
performance if overvoltage trips occur.
• Gradually reduce the setting in 2 ms increments and check the
performance if response is slow.
Note: Ensure that C4-02 ≤ C4-06. When changing C4-06
(Torque Compensation Primary Delay Time Constant 2),
increase the value of n2-03 proportionally.
• Gradually reduce the setting in 2 ms increments and check the
performance to improve motor torque speed response.
• Gradually increase the setting in 10 ms increments if motor
hunting and oscillation occur.
Note: Ensure that C4-02 ≤ C4-06. When making adjustments
to C4-02, increase the AFR time constant (n2-02)
proportionally.
• Gradually reduce the setting in 10 ms increments if response is
slow.
• Gradually increase the setting in 10 ms increments if speed is
unstable.
• Gradually increase the setting in 0.1 ms increments if speed is too
slow.
• Gradually reduce the setting in 0.1 ms increments if speed is too
fast.
Enable slip compensation during regeneration by setting parameter
C3-04 = 1.
• Increase the carrier frequency if there is too much motor noise.
• Reduce the carrier frequency if motor hunting and oscillation
occur at low speeds.
Note: The default setting for the carrier frequency depends on
the drive capacity (o2-04) and Duty Selection (C6-01).
• Increase the setting if motor torque and speed response are too
slow.
• Reduce the setting if the motor exhibits excessive instability at
start-up.
Note: When working with a relatively light load, increasing
this value too much can cause overtorque.
6.2 Motor Performance Fine-Tuning
Corrective Action
Suggested
Default
Setting
1.00
0.50 to 2.00
50 ms
50 to 2000 ms
750 ms
750 to 2000 ms
150 ms
150 to 750 ms
<1>
<1>
20 ms
20 to 100 ms
<2>
100 to 500 ms
200 ms
<2>
0.5 to 1.5
1.0
0
1
1 (2 kHz)
0 to max. setting
E1-08:
11.0 V
<2>
Default setting
E1-10:
±2 V
2.0 V
<2>