D4: Frequency Reference Hold And Up/Down 2 Function - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
d3-04
Jump Frequency Width
(297)
<1> Default setting is determined by parameter A1-02, Control Mode Setting.
u

d4: Frequency Reference Hold and Up/Down 2 Function

No.
(Addr.
Name
Hex)
d4-01
Frequency Reference Hold
(298)
Function Selection
d4-03
Frequency Reference Bias
(2AA)
Step (Up/Down 2)
d4-04
Frequency Reference Bias
(2AB)
Accel/Decel (Up/Down 2)
d4-05
Frequency Reference Bias
(2AC)
Operation Mode Selection
(Up/Down 2)
d4-06
Frequency Reference Bias
(2AD)
(Up/Down 2)
d4-07
Analog Frequency
(2AE)
Reference Fluctuation Limit
(Up/Down 2)
d4-08
Frequency Reference Bias
(2AF)
Upper Limit (Up/Down 2)
d4-09
Frequency Reference Bias
(2B0)
Lower Limit (Up/Down 2)
d4-10
Up/Down Frequency
(2B6)
Reference Limit Selection
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
All Modes
Sets the dead-band width around each selected prohibited frequency reference
point.
Description
All Modes
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency that
was saved.
All Modes
Sets the bias added to the frequency reference when the Up 2 and Down 2
digital inputs are enabled (H1-oo = 75, 76).
All Modes
0: Use selected accel/decel time.
1: Use accel/decel time 4 (C1-07 and C1-08).
All Modes
0: Bias value is held if no input Up 2 or Down 2 is active.
1: When the Up 2 reference and Down 2 reference are both on or both off, the
applied bias becomes 0. The specified accel/decel times are used for
acceleration or deceleration.
All Modes
The Up/Down 2 bias value is saved in d4-06 when the frequency reference is
not input by the digital operator. Set as a percentage of the maximum output
frequency.
All Modes
Limits how much the frequency reference is allowed to change while an input
terminal set for Up 2 or Down 2 is enabled. If the frequency reference changes
for more than the set value, then the bias value is held and the drive accelerates
or decelerates to the frequency reference. Set as a percentage of the maximum
output frequency.
All Modes
Sets the upper limit for the bias and the value that can be saved in d4-06. Set
as a percentage of the maximum output frequency.
All Modes
Sets the lower limit for the bias and the value that can be saved in d4-06. Set
as a percentage of the maximum output frequency.
All Modes
0: The lower limit is determined by d2-02 or an analog input.
1: The lower limit is determined by d2-02.
B.6 d: References
Values
Page
<1>
Default:
172
Min.: 0.0
Max.: 20.0
Values
Page
Default: 0
173
Range: 0, 1
Default: 0.00 Hz
Min.: 0.00
175
Max.: 99.99
Default: 0
176
Range: 0, 1
Default: 0
176
Range: 0, 1
Default: 0.0%
Min.: -99.9
176
Max.: 100.0
Default: 1.0%
Min.: 0.1
177
Max.: 100.0
Default: 0.0%
Min.: 0.0
177
Max.: 100.0
Default: 0.0%
Min.: -99.9
177
Max.: 0.0
Default: 0
177
Range: 0, 1