YASKAWA AC Drive-A1000 Technical Manual page 418

High performance vector control drive
Table of Contents

Advertisement

B.9 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
68
High slip braking
6A
Drive enable
71
Speed/Torque control Sswitch
72
Zero servo
75
Up 2 command
76
Down 2 command
77
ASR gain switch
External torque reference polarity
78
inversion
7A
KEB Ride-Thru 2 (N.C.)
7B
KEB Ride-Thru 2 (N.O.)
7C
Short circuit braking (N.O.)
7D
Short circuit braking (N.C.)
Forward/reverse detection
7E
(V/f Control with Simple PG
feedback)
DriveWorksEZ
90 to 97
digital inputs 1 to 8
9F
DriveWorksEZ disable
418
H1 Multi-Function Digital Input Selections
V/f
V/f
V/f w PG
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Closed: Activates High Slip Braking to stop the drive.
All Modes
Open: Drive disabled. If this input is opened during run, the drive will stop as specified by
b1-03.
Closed: Ready for operation.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Open: Speed Control
Closed: Torque Control
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Closed: Zero Servo enabled.
All Modes
Used to control the bias added to the frequency reference by the Up/Down 2 function. The
Up 2 and Down 2 commands must always be used in conjunction with one another.
All Modes
Used to control the bias added to the frequency reference by the Up/Down 2 function. The
Up 2 and Down 2 commands must always be used in conjunction with one another.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
Open: ASR proportional gain 1 (C5-01).
Closed: ASR proportional gain 2 (C5-03).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Open: Forward torque reference.
Closed: Reverse polarity.
All Modes
Open: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB
Ride-Thru 2.
All Modes
Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB
Ride-Thru 2.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Closed: Short Circuit Braking enabled.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Open: Short Circuit Braking enabled.
V/f
V/f w PG
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Direction of rotation detection (for V/f with Simple PG Feedback).
All Modes
Reserved for DWEZ input functions.
All Modes
Open: DWEZ enabled.
Closed: DWEZ disabled.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
Page
216
216
216
216
216
216
217
217
217
217
217
217
217
218
218

Hide quick links: