4.11 Test Run Checklist

Review the checklist before performing a test run. Check each item that applies.
No.
1
Thoroughly read the manual before performing a test run.
2
Turn the power on.
3
Set the voltage for the power supply to E1-01.
4
Select the correct duty rating (C6-01) for the application.
Check the items that correspond to the control mode being used.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing
the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary
closure on terminal S1 may cause the drive to start.
No.
V/f Control (A1-02 = 0) and V/f Control with PG (A1-02 = 1)
5
Select the best V/f pattern according to the application and motor characteristics.
6
Perform Rotational Auto-Tuning for V/f Control if using Energy Saving functions.
V/f Control with PG (A1-02 = 1)
7
Set up the PG feedback parameters correctly and make sure the encoder pulse counting direction is correct.
8
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02.
Open Loop Vector Control (A1-02 = 2) or Closed Loop Vector Control (A1-02=3)
9
Perform Auto-Tuning as described.
Closed Loop Vector Control (A1-02 = 3)
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. Perform ASR Tuning if
10
possible.
Open Loop Vector Control for PM (A1-02 = 5)
11
Perform Auto-Tuning as described.
Advanced Open Loop Vector Control for PM (A1-02 = 6)
12
Perform Auto-Tuning as described.
13
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02.
Closed Loop Vector Control for PM (A1-02 = 7)
14
Perform Auto-Tuning as described.
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. Perform ASR Tuning if
15
possible.
16
Set the encoder Z Pulse offset in parameter E5-11.
Proceed to the following checklist after checking items 5 through 16.
No.
17
The
To give a Run command and frequency reference from the digital operator, press
18
The LO/RE key will light.
If the motor rotates in the opposite direction during the test run, switch two of the drive output terminals
20
(U/T1, V/T2, W/T3) or change parameter b1-14.
Set the correct values for the motor rated current (E2-01, E4-01, E5-03) and motor protection (L1-01) to ensure
21
motor thermal protection.
If the Run command and frequency reference are provided via the control circuit terminals, set the drive for REMOTE
22
and be sure the LO/RE light is out.
If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level (0
23
to 10 V) or the correct current input signal level (4 to 20 mA or 0 to 20 mA).
24
Set the proper voltage to terminal A1 and A3 (-10 to +10 V).
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
should light after giving a Run command.
Checklist
Checklist
Checklist

4.11 Test Run Checklist

Page
96
184
Page
100
196
163
106
163
108
108
163
108
163
108
Page
to set to LOCAL.
89
96
89
126
126
4
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents