Control Mode Dependent Parameter Default Values; Control Mode Dependent Parameter Default Values; A1-02 Dependent Parameters - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

B.4 Control Mode Dependent Parameter Default Values
B.4 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection. These parameters are initialized to the shown
values if the control mode is changed.

◆ A1-02 Dependent Parameters

No.
b2-01
DC Injection Braking Start Frequency
b2-04
DC Injection Braking Time at Stop
b3-01
Speed Search Selection at Start
b3-02
Speed Search Deactivation Current
b5-15
PID Sleep Function Start Level
b8-01
Energy Saving Control Selection
C1-11
Accel/Decel Time Switching Frequency
C2-01
S-Curve Time at Acceleration Start
C4-01
Torque Compensation Gain
C4-02
Torque Compensation Primary Delay Time
C6-02
Carrier Frequency Selection
d3-01
Jump Frequency 1
d3-02
Jump Frequency 2
d3-03
Jump Frequency 3
d3-04
Jump Frequency Width
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-07
Middle Output Frequency
E1-08
Middle Output Frequency Voltage
E1-09
Minimum Output Frequency
E1-10
Minimum Output Frequency Voltage
L1-01
Motor Overload Protection Selection
L3-20
DC Bus Voltage Adjustment Gain
L3-21
Accel/Decel Rate Calculation Gain
L4-01
Speed Agreement Detection Level
L4-02
Speed Agreement Detection Width
L4-03
Speed Agreement Detection Level (+/-)
L4-04
Speed Agreement Detection Width (+/–)
L8-38
Carrier Frequency Reduction Selection
L8-40
Carrier Frequency Reduction Off Delay Time
o1-03
Digital Operator Display Selection
<9> Default setting is determined by the drive model (o2-04).
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<52> This setting value depends on a Maximum Applicable Motor Capacity and V/f pattern selection in parameter E1-03.
<53> This setting value depends on a Maximum Applicable Motor Capacity: 1000 s in models CIMR-E2A0110 to 2A0415 and CIMR-
E4A0103 to 4A1200.
398
Table B.2 A1-02 Dependent Parameters and Default Values
Name
<18>
<18>
<18>
Setting Range
0.0 to 10.0
0.00 to 10.00
0 to 1
0 to 200
0.0 to 200.0
0 to 1
0.0 to 200.0
0.00 to 10.00
0.00 to 2.50
0 to 10000
1 to F
0.0 to 200.0
0.0 to 200.0
0.0 to 200.0
0.0 to 20.0
40.0 to 200.0
0.0 to 255.0
0.0 to 200.0
0.0 to 200.0
0.0 to 255.0
0.0 to 200.0
0.0 to 255.0
0 to 4
0.00 to 5.00
0.00 to 200.00
0.0 to 200.0
0.0 to 20.0
-200.0 to 200.0
0.0 to 20.0
0 to 2
0.00 to 2.00
0 to 3
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Control Modes (A1-02)
Resolution
V/f (0)
0.1
0.5 Hz
0.01 s
0.50
0
1%
120
0.1
0.0 Hz
0
0.1
0.0 Hz
0.01 s
0.20
0.01
1.00
1 ms
200
<53>
0.0 Hz
0.1
0.0 Hz
0.1
0.0 Hz
0.1
0.0 Hz
0.1
1.0 Hz
0.1 Hz
60.0
0.1 V
200.0
<52>
0.1 Hz
50.0
<52>
0.1 Hz
3.0
<52>
0.1 V
15.0
<52>
0.1 Hz
1.5
<52>
0.1 V
9.0
1
0.01
1.00
0.01
1.00
0.1
0.0 Hz
0.1
2.0 Hz
0.1
0.0 Hz
0.1
2.0 Hz
1
<9>
0.01 s
0.50
1
0
OLV/PM (5)
0.5 Hz
0.00
0
0.0 Hz
0.0 Hz
1.00
0.00
100
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
1.0 Hz
<14>
<14>
<14>
<14>
4
0.65
2.50
0.0 Hz
2.0Hz
0.0 Hz
2.0Hz
0
0.00
0